AC-DC Batter Charger3 phase battery charger power supply

3 phase battery charger power supply

l Output overvoltage protection

To prevent the disastrous accident caused by output overvoltage to electric consumers, there is overvoltage protection circuit in the module. When output overvoltage occurs, the module locks up automatically, the relative module fault indication light is on, the faulty module quits work automatically and doesn’t affect the normal operation of the entire system.

l Output current limiting protect

The output current cannot increase infinitely. The maximum value of the output current of each module is limited to the rated output current 105%, in this range, the output current value of the module is continuously adjustable. If the load output of the module, the module will play down the output voltage

l Output short-circuit protection

When output short circuit, the module draws the output voltage to 0 immediately, limit the short circuit current below 15%limit current point to protect the module. The module will not be damaged under short circuit state for a long time, and can go back to work automatically after debugging.

l Module parallel protection

There is parallel protection circuit in each module to ensure that when the fault module quits the system, the normal work of other modules and the system won’t be effect.

Over-temperature protection

Over-temperature protection is mainly for protecting large power converters, under normal operating circumstance, the module design leaves enough margin, under special circumstance, when the module detects that the temperature of the radiator is over 90℃, it will shut down automatically to protect itself. When the temperature of radiator get down,  the module will restart work automatically.

l Output over-current protection

Because of the limit of the module output power, the output current cannot increase infinitely. In the range, the output current value of the module is continuously adjustable. If overloaded, the module can reduce output voltage automatically to make it not surplus the rated output limit point in order to protect the power components. The over current protection can be resumed automatically.

 

Technical specification

Model  BZA

230D10NZ-D

230D20NZ-3

230D30NZ-3

230D40NZ-3

110D20NZ-5

AC input

Input voltage

380VAC±20%

380VAC±15%

Input phase

3-Phase

Power factor

≥93%

Input frequency

45 to 65Hz

DC output

Output voltage

190-300VDC (Nominal 220VDC)

95-150VDC (Nominal 110VDC)

Default output voltage

234VDC

117VDC

Rated output current

10A

20A

30A

40A

20A

Max output power

3000W

6000W

9000W

12000W

3000W

Output current limit

105% rated output current

Efficiency

≥93

Voltage accuracy

±0.5%

Current accuracy

±1%

Ripple

≤0.2%

Load share imbalance

≤±3%

Features

Communication interface

CAN/RS485

RS485

Load capability

100% continuous output current

Indicators

LED indicator for AC mains, rectifier failure;

Digit fault code on LCD display,

Protection and alarms

Input under/over voltage, output under/over voltage, output current limit, over temperature, short circuit protection, phase loss

Insulation

2.1kVac input-earth

2.1kVac input-output

2.1kVac output-earth

Mechanical

Weight (kgs)

4.5kgs

10.5kgs

19kgs

19kgs

5kgs

Dimension(H/W/D)

160/67/299.5

218/118/357

303/136/410

303/136/410

195/91/303

 (Enclosure) (mm)

Dimension (H/W)

178/71

254/124

340/145

340/145

194.5/90.5

(front panel) (mm)

Front panel

Plastic

Environmental

Cooling Method

Force-air cooling

Noise(dB)

Storage temperature

-40/+60℃

working temperature

-10/+40℃

Humidity

95% RH non-condensing

Altitude

≤2000m